GI 1000 LX ME 50Hz - Burners Baltur

GI 1000 LX ME 50Hz

Code 66570050

Modulating gas burners with low polluting emissions with electronic modulation.

  • Electronic modulation.
  • Low NOx emissions.
Technical data
Fuel
Natural Gas
Operation
Electronic Modulation
Minimum Thermal Power (kW) to ErP
1500
Maximum Thermal Power (kW) to ErP
10850
Min flow rate (Sm³/H)
159
Max flow rate (Sm³/H)
1148
Electric power supply type
AC
No. of Phases
3N
Power Supply Voltage (V)
400
Power Supply Frequency (Hz)
50
Fan Motor Power (kW)
22
Weight without packaging (kg)
580
Weight with packaging (kg)
680
Width (mm)
2610
Depth (mm)
1760
Height (mm)
1470
Technical Descriptions
Modulation ratio 1:7.
Gas burner with low NOx and CO emissions in accordance with European standard EN676: class 3.
Regulating combustion air and blast-pipe.
Combustion air intake with throttle damper. Air flow adjustment with electric servomotor.
Fully closing air damper on shutdown to avoid loss of heat through the chimney.
Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler.
Fixed boiler coupling flange.
Easy maintenance thanks to the two-sides hinge which allows the removal of the combustion head without having to remove the burner from the boiler.
Ignition gas train complete with operation and safety valve, min. pressure switch, pressure regulator and gas filter.
CE version main gas train is complete with operation and safety valve with electromagnetic drive, valve tightness control, minimum and maximum pressure switch, pressure regulator and gas filter.
Flame presence control with IRT photocell
Control panel equipped either with display showing the working process and with the keyboard for the burner adjustment.
Terminal board for the electric feeding and for the connection to the modulation probe.
Electric protection rating:
Documents
Public documents
Type summary
Revision
Publish Date
Languages
Use and maintenance manual
201109
 
Use and maintenance manual
201109
 
Use and maintenance manual
200608
 
Reserved documents
Operating range

This product is part of the range GI LX ME

Discover the entire series
Login
Cookies help us deliver our services. Using these services, you agree to the use of cookies on our part. Info